Heat pump water-air split system

The use of split systems with heat pump is one of the main innovations in the field of conditioning and ventilation systems in recent times. Low energy consumption is also one of the advantages of split system with heat pump of water-air type. This type of system is usually used in houses, stores, cafes, restaurants, office buildings etc.

Features of Menergy split system:

  • Due to big diameter of tubular heat exchanger, a high efficiency of heat exchange, reliable operation and high indicators of freeze resistance are guaranteed.
  • Coolants R-410A, R-407C and R-22 are used as an option.
  • Noiseless operation is provided due to unique anti-vibration technologies (licence ZL 2020 2 0243049.7) and use of modern acoustic absorber materials.
  • The intelligent microcomputer is responsible for system control. It is a simple and automatic man-machine control interface on a large LCD-display.
  • The possibility of centralized control and ON/OFF internet booking is provided due to unique patent developments (Licence ZL 2010 2 0243047.8)

It is important to know! In order to avoid the additional financial expenses, it is necessary to determine the equipment capacity you need. There are all technical parameters below, with the help         of which you will be able to make a right choice. For more information, contact our company by telephone numbers: +999 (71) 207 33 32.

 Technical parameters:

Water Loop

Model Internal 2600FY 3500FY 4500FY 5800FY 7200FY 8600FY 10500FY 12600FY 14600FY
External 2600W 3500W 4500W 5800W 7200W 8600W 10500W /S 12600W /S 14600W
Nominal cooling capacity (KW) 2.6 3.5 4.5 5.8 7.2 8.6 10.5 12.6 14.6
EER 4.64 4.27 4.41 4.30 4.37 4.43 4.12 4.17 4.21
Nominal heating capacity (KW) 3.00 3.95 5.10 6.48 8.10 9.40 11.40 13.60 15.80
COP 4.76 4.65 4.64 4.47 4.66 4.63 4.21 4.20 4.27
Air consumption (m3/h) 500 700 910 1190 1480 1760 2150 2570 3010
Internal static pressure (Pa) 12(8) 20(12) 30(20) 50(30)
Input power in cooling (KW) 0.59 0.82 1.02 1.35 1.65 1.94 2.51 3.02 3.47
Input power in heating (KW) 0.63 0.85 1.10 1.45 1.74 2.03 2.71 3.24 3.70
Electric parameters (V/Ph/Hz) 230/1/50 380~420/3/50
Input current in cooling (A) 2.7 3.9 4.9 6.5 7.8 9.3 3.9 4.7 5.4
Input current in heating (A) 3.0 4.0 5.2 6.9 8.2 9.7 4.2 5.0 5.7
Type/number of compressors Rotational/1 Spiral/1
Noise level dB(A) Internal 35 35 37 37 40 41 42 42 42
External 30 31 32 32 35 36 36 38 38
Dimension
(LxWxH)
Internal 855*475
*235
1005*475
*235
1125*475
*235
1355*475
*235
1605*475
*235
1750*475
*235
2005*475
*235
2065*490*285
External 550*430*385 590*430
*385
550*490
*420
635*520*510 695*520
*535
720*580*535
Weight (kg) Internal 18 22 26 30 34 36 40 50 55
External 34 35 40 48 66 68 90 90 100
Water consumption (m3/h) 0.58 0.72 0.92 1.25 1.52 1.85 2.25 2.66 3.12
Water pressure drop (Pa) 18 22 30 35 35 35 35 38 38
Connecting pipe Liquid (mm) Ø6×0.75 Ø9.52×0.75 Ø12.7×0.75
Gas (mm) Ø9.52×0.75 Ø12.7×0.75 Ø16×1.0 Ø19×1.0
Chilled water pipe (diameter) R3/4(DN20) R1(DN25) R1-1/4(DN32)
Condensate pipe (diameter) R3/4(DN20)
Volume (kg) 0.65 0.84 0.95 1.1 1.5 1.8 2.1 2.3 2.8

Attention:

  1. In cooling mode: air temperature on dry/wet thermometer is 27 ℃/19℃; water temperature is 30℃/35℃ (inlet/outlet).
  2. In heating mode: air temperature on dry/wet thermometer is 20 ℃/15℃; water temperature at the inlet is 20 ℃.
  3. The equipment with only cooling function doesn’t have parameters in the heating mode.
  4. Menergy Company reserves the right to update the parameters

Ground water

Model Internal 2600FY 3500FY 4500FY 5800FY 7200FY 8600FY 10500FY 12600FY 14600FY
External 2600W 3500W 4500W 5800W 7200W 8600W 10500W /S 12600W /S 14600W
Nominal cooling capacity (KW) 2.6 3.5 4.5 5.8 7.2 8.6 10.5 12.6 14.6
EER 4.73 4.43 4.09 4.46 4.44 4.57 4.36 4.41 4.79
Nominal heating capacity (KW) 2.80 3.70 4.50 5.70 7.30 8.70 10.40 12.50 14.50
COP 4.59 4.51 4.09 4.29 4.17 4.46 4.05 4.15 4.53
Cooling capacity (USRT) 0.74 1.00 1.29 1.66 2.06 2.46 3.00 3.60 4.17
Heating capacity (USRT) 0.80 1.06 1.29 1.63 2.09 2.49 2.97 3.49 4.14
Air consumption (m3/h) 520 715 910 1190 1480 1760 2150 2570 3010
Internal static pressure (Pa) 12(8) 20(12) 30(20) 50(30)
Input power in cooling (KW) 0.55 0.79 1.1 1.3 1.62 1.88 2.41 2.86 3.05
Input power in heating (KW) 0.61 0.82 1.10 1.33 1.75 1.95 2.57 3.01 3.20
Electric parameters (V/Ph/Hz) 230/1/50 380~420/3/50
Input current in cooling (A) 2.7 3.8 5.1 6.3 7.8 8.6 4.6 5.5 5.8
Input current in heating (A) 2.9 3.9 5.1 6.4 8.4 8.4 4.9 5.8 6.2
Type/number of compressors Rotational/1 Spiral/1
Noise level dB(A) Internal 35 35 37 40 48 48 52 54 55
External 30 31 32 35 46 40 48 51 52
Dimensions
(LxWxH)
Internal 855*475
*235
1005*475
*235
1125*475
*235
1355*475
*235
1605*475
*235
1750*475
*235
2005*475
*235
2065*490*285
External 550*430*385 550*430*420 635*520*510 695*520
*535
720*580*535
Weight (kg) Internal 18 22 28 30 34 36 40 50 55
External 34 35 40 46 66 75 90 90 100
Water consumption (m3/h) 0.27 0.38 0.5 0.61 0.78 0.96 1.07 1.31 1.5
Water pressure drop (Pa) 8.4 10.6 11 11.6 10.8 13.5 30.2 42 45
Connecting pipe Liquid (mm) Ø6×0.75 Ø9.52×0.75 Ø12.7×0.75
Gas (mm) Ø9.52×0.75 Ø12.7×0.75 Ø16×1.0 Ø19×1.0
Chilled water pipe (diameter) R3/4(DN20) R1(DN25) R1-1/4(DN32)
Condensate pipe (diameter) R3/4(DN20)
Volume (kg) 0.65 0.84 0.95 1.1 1.5 1.7 2.0 2.3 2.5

Attention:

  1. In cooling mode: air temperature on dry/wet thermometer is 27 ℃/19℃; water temperature is 30℃/35℃ (inlet/outlet).
  2. In heating mode: air temperature on dry/wet thermometer is 20 ℃/15℃; water temperature at the inlet is 15 ℃.
  3. The equipment with only cooling function doesn’t have parameters in the heating mode.
  4. Menergy Company reserves the right to update the parameters

 

Underground loop

Model Internal 2600FY 3500FY 4500FY 5800FY 7200FY 8600FY 10500FY 12600FY 14600FY
External 2600W 3500W 4500W 5800W 7200W 8600W 10500W /S 12600W /S 14600W /S
Nominal cooling capacity (KW) 3.5 4.5 5.8 7.2 8.6 10.5 12.6 14.6
EER 4.49 4.25 4.20 4.19 4.28 4.27 4.16 4.35
Nominal heating capacity (KW) 3.20 4.10 5.30 6.60 7.90 9.60 11.50 13.10
COP 4.21 4.06 4.21 4.15 4.34 3.95 4.05 4.34
Cooling capacity (USRT) 1.00 1.29 1.66 2.06 2.46 3.00 3.60 4.17
Heating capacity (USRT) 0.91 1.17 1.46 1.86 2.23 2.68 3.08 3.57
Air consumption (m3/h) 715 910 1190 1480 1760 2150 2570 3010
Internal static pressure (Pa) 20(12) 30(20) 50(30)
Input power in cooling (KW) 0.78 1.06 1.38 1.72 2.01 2.46 3.03 3.36
Input power in heating (KW) 0.76 1.01 1.26 1.59 1.82 2.43 2.84 3.02
Electric parameters (V/Ph/Hz) 380~420/3/50
Input current in cooling (A) 3.7 5.1 6.6 8.2 9.2 4.7 5.8 6.5
Input current in heating (A) 3.6 4.8 6.0 7.6 8.3 4.7 5.5 5.8
Type/number of compressors Спиральный/1
Noise level dB(A) Internal 35 35 37 37 40 48 52 54 55
External 30 31 32 35 46 40 48 51 52
Dimensions
(LxWxH)
Internal 855*475
*235
1005*475
*235
1125*475
*235
1355*475
*235
1605*475
*235
1750*475
*235
2005*475
*235
2065*490*285
External 550*430*385 550*430*420 635*520*510 695*520
*535
720*580*535
Weight (kg) Internal 18 22 28 30 34 36 40 50 55
External 34 35 40 46 66 75 90 90 100
Water consumption (m3/h) 0.8 0.95 1.29 1.61 1.95 2.28 2.83 3.25
Water pressure drop (Pa) 12.6 13.6 13.2 14.4 22 33.9 45.2 47
Connecting pipe Liquid (mm) Ø6×0.75 Ø9.52×0.75 Ø12.7×0.75
Gas (mm) Ø9.52×0.75 Ø12.7×0.75 Ø16×1.0 Ø19×1.0
Chilled water pipe (diameter) R1(DN25) R1-1/4(DN32)
Condensate pipe (diameter)
Volume (kg) 0.7 0.95 1 1.3 1.7 2 2.3 2.5

Attention:

  1. In cooling mode: air temperature on dry/wet thermometer is 27 ℃/19℃; water temperature is 25℃/30℃ (inlet/outlet).
  2. In heating mode: air temperature on dry/wet thermometer is 20 ℃/15℃; water temperature at the inlet is 10 ℃.
  3. The equipment with only cooling function doesn’t have parameters in the heating mode.
  4. Menergy Company reserves the right to update the parameters