Fan coil unit is an important element in conditioning system of the most modern buildings. It is worth noting that the main outstanding feature of this equipment is that they don’t require the installation of outdoor unit on the walls of the building. Fan coils are operated with air conditioners. They are widely used in the apartments, stores, offices and hospitals.

Fan coils Canada Menergy is a complex device, consisting of fan, heat exchanger and electric elements. Fan rotation has several stages of speed. Operation with condenser allows to consume low electric energy.

Properties of the equipment:

  • The ability of selection of 2 or 3 pipes models.
  • Nice appearance perfectly fits with any conditions.
  • Motor and fan provide the best efficiency, low noise level and stable operation.
  • Material production – sheet of galvanized steel.
  • The symmetry construction is adapted to any conditions. Pipe connection can be carried out both from right and left sides.
  • The use of hydrophilic aluminum foil decently improves the corrosion resistance and other types of chemical destruction of the metal.

Model range of ducted fan coil units from Canada Menergy includes more than 25 types. In order to make a right choice of fan coil unit, please fill in the “questionnaire for equipment selection” or call us by one of the telephone numbers listed in the section “Contacts”.

Fan coil unit (Hidden type) Two pipes

Model MFP
34-2
MFP
51-2
MFP
68-2
MFP
85-2
MFP
102-2
MFP
136-2
MFP
170-2
MFP
204-2
MFP
238-2
Cooling capacity W 1800 2700 3600 4500 5400 7200 9000 10800 12600
Heating capacity 3400 4100 5400 6800 8100 10800 13500 16200 18900
Electric parameters(V/Ph/Hz) 230/1/50
Air consumption
(m3/h)
High 400 550 780 900 1060 1500 1800 2140 2500
Medium 330 450 590 680 800 1100 1350 1560 1960
Low 260 290 400 450 560 740 900 1100 1250
Power consumption Standard 37 52 62 75 96 134 152 189 228
30 Pa static press 44 59 72 87 108 156 174 212 253
50 Pa static press 49 66 84 100 118 174 210 250 300
Water consumption (kg/h) 330 465 620 755 930 1239 1548 1857 2160
Water resistance 5 8 16 23 32 10 20 30
Fan& Мotor Type Centrifugal
Fan 1 2 2 2 2 3 4 4 4
Motor 1 1 1 1 1 2 2 2 2
Noise level (dB/A) Standard ≤35 ≤36 ≤39 ≤42 ≤45 ≤44 ≤46 ≤49 ≤50
30 Pa static press ≤39 ≤40 ≤43 ≤44 ≤47 ≤48 ≤49 ≤51 ≤52
50 Pa static press ≤41 ≤43 ≤44 ≤46 ≤49 ≤50 ≤51 ≤53 ≤54
Dimensions Length (mm) 750 850 920 1050 1250 1650 1850 1950 2050
Width (mm) 465 465 465 465 465 465 465 465 465
Height (mm) 240 240 240 240 240 240 240 240 240
Size of pack Length (mm) 772 872 972 1072 1276 1676 1876 1976 2076
Width (mm) 480 480 480 480 480 480 480 480 480
Height (mm) 260 260 260 260 260 260 260 260 260
Pipe coil Copper pipes with double ribs (1.8мм); working pressure 1.6MPa
Pipe inlet/outlet RC3/4″(DN20) RC3/4″(DN20) RC3/4″(DN20)
Netto weight(Kg) 12 14 15 17 18 26 30 32 36

Attention:

  • Cooling mode: air temperature inside room by dry/wet thermometer 27℃(80.6℉)/19℃(66.2℉); water temperature 7℃(44.6℉).
  • Heating mode: air temperature inside the room by dry thermometer 21℃(69.8℉); water temperature is 60℃(140℉).
  • Menergy reserves the unique right to update technical parameters, please refer to the table

 

Three pipes

Model Model MFP
51-3
MFP
68-3
MFP
85-3
MFP
102-3
MFP
136-3
MFP
170-3
MFP
204-3
MFP
238-3
Cooling capacity Cooling capacity

Heating capacity

1800 2700 3600 4500 5400 7200 9000 10800 12600
Heating capacity 3400 4100 5400 6800 8100 10800 13500 16200 18900
Electric parameters(V/Ph/Hz) Electric parameters(V/Ph/Hz)
Air consumption
(m3/h)
High 400 550 680 900 1060 1500 1800 2140 2500
Medium 330 450 590 680 800 1100 1350 1560 1960
Low 260 290 400 450 560 740 900 1100 1250
Power consumption Standard 37 52 62 75 96 134 152 189 228
30 Pa static press 44 59 72 87 108 156 174 212 253
50 Pa static press 49 66 84 100 118 174 210 250 300
Water consumption (kg/h) 330 465 620 755 930 1239 1548 1857 2160
Water resistance 5 8 16 23 32 10 20 30
Fan & Motor Type Centrifugal
Fans 1 2 2 2 2 3 4 4 4
Motor 1 1 1 1 1 2 2 2 2
Noise level (dB/A) Standard ≤35 ≤36 ≤39 ≤42 ≤45 ≤44 ≤46 ≤49 ≤50
30 Pa static press ≤39 ≤40 ≤43 ≤44 ≤47 ≤48 ≤49 ≤51 ≤52
50 Pa static press ≤41 ≤43 ≤44 ≤46 ≤49 ≤50 ≤51 ≤53 ≤54
Dimensions Length (mm) 750 850 920 1050 1250 1650 1850 1950 2050
Width (mm) 465 465 465 465 465 465 465 465 465
Height (mm) 240 240 240 240 240 240 240 240 240
Size of packing Length (mm) 772 872 972 1072 1276 1676 1876 1976 2076
Width (mm) 480 480 480 480 480 480 480 480 480
Height (mm) 260 260 260 260 260 260 260 260 260
Coil pipe Copper pipes with double ribs (1.8mm); working pressure 1.6MPa
Pipe inlet/outlet RC3/4″(DN20) RC3/4″(DN20) RC3/4″(DN20)
Netto weight(Kg) 12 14 15 17 18 26 30 32 36

Attention:

  • Cooling mode: air temperature inside room by dry/wet thermometer 27℃(80.6℉)/19℃(66.2℉); water temperature 7℃(44.6℉).
  • Heating mode: air temperature inside the room by dry thermometer 21℃(69.8℉); water temperature is 60℃(140℉).
  • Menergy reserves the unique right to update technical parameters, please refer to the table

 

Four pipes (three pipes for cooling and one pipe for heating)

Model Model MFP
51-3+1
MFP
68-3+1
MFP
85-3+1
MFP
102-3+1
MFP
136-3+1
MFP
170-3+1
MFP
204-3+1
MFP
238-3+1
Cooling capacity Cooling capacity

Heating capacity

1970 2860 3700 4500 5400 7200 9000 10800 12600
Heating capacity 1810 2390 3270 3830 4690 6240 6920 8110 9450
Electric parameters(V/Ph/Hz) Electric parameters(V/Ph/Hz)
Air consumption
(m3/h)
High 340 510 680 850 1020 1360 1700 2040 2380
Fan 270 380 510 640 780 1020 1290 1530 1870
Motor 190 290 340 450 530 750 890 1040 1230
Power consumption Standard 42 55 65 82 102 146 168 190 250
30 Pa static press 47 62 75 95 110 165 190 230 280
50 Pa static press 340 490 645 790 935 1250 1550 1857 2230
Water consumption (kg/h) 201 269 372 440 538 734 824 977 1152
Water resistance 8 17 27 20 28 30 38 40 46
Fan & Motor Type 12 20 31 33 33 35 41 44 48
Fans Centrifugal / Центробежный
Motors 1 2 2 2 2 3 4 4 4
Noise level (dB/A) Standard 1 1 1 1 1 2 2 2 2
30 Pa static press ≤35 ≤36 ≤39 ≤42 ≤45 ≤44 ≤46 ≤49 ≤50
50 Pa static press ≤39 ≤40 ≤43 ≤44 ≤47 ≤48 ≤49 ≤51 ≤52
Dimensions Length (mm) 750 850 920 1050 1250 1650 1850 1950 2050
Width (mm) 465 465 465 465 465 465 465 465 465
Height (mm) 240 240 240 240 240 240 240 240 240
Size of packing Length (mm) 772 872 972 1072 1276 1676 1876 1976 2076
Width (mm) 480 480 480 480 480 480 480 480 480
Height (mm) 260 260 260 260 260 260 260 260 260
Coil pipe Copper pipes with double ribs (1.8mm); working pressure 1.6MPa
Pipe inlet/outlet RC3/4″(DN20) RC3/4″(DN20) RC3/4″(DN20)
Weight Netto(Kg) 17 19 23 25 27 34 42 48 54

Attention:

  • Cooling mode: air temperature inside room by dry/wet thermometer 27℃(80.6℉)/19℃(66.2℉); water temperature 5℃(41℉).
  • Heating mode: air temperature inside the room by dry thermometer 21℃(69.8℉); water temperature is 60℃(140℉).
  • Menergy reserves the unique right to update technical parameters, please refer to the table