Description
Model | IWCQWRF160MG | |||
Capacity | Cooling (kW) | 143 | ||
Heating (kW) | 160 | |||
EER (W/W) | 2.68 | |||
COP (W/W) | 3.0 | |||
Power supply (V/F/Hz) | 380V-415V/3ф/50Hz | |||
Powe consumption | Cooling (kW) | 53.4 | ||
Heating (kW) | 53.3 | |||
Water heat exchanger | Type | High efficient shell and tube evaporator | ||
Volume of water flow | m3/h | 24.5 | ||
l/s | 6.8 | |||
Pressure drop | kPa | 35 | ||
ft.WG | 11.5 | |||
Pipes of connection (mm) | DN50 | |||
Air heat exchanger | Fan | Type/quantity | axial fan / 6 | |
General air flow | m3/h | 6.4 x 104 | ||
CFM | 3.8 x 104 | |||
General fan’s capacity (W) | 700 x 6 | |||
Level of sound pressure (dB (А)) | 70 | |||
Dimension | Device (W x D x H) (mm) | 2200x2265x2214 | ||
With package (W x D x H) (mm) | 2230x2295x2214 | |||
Netto weight (kg) | 2 080 |