Description
Technical characterisitis CyberAir 2 С1 |
||
Units CW ( the first circuit of chilled water) | ||
ASD/ASU xxx CW | 400 | |
Air consumption | m3/h | 8500 |
Cooling capacity CW (full)1) Water temperature: 7 °С/12 °С |
kW | 38.8 |
Cooling capacity CW (actual)1) Water temperature: 7 °С/12 °С |
kW | 33.1 |
Pressure drop in hydrosystem Water temperature: 7 °С/12 °С |
kPa | 58 |
Cooling capacity CW (full) 1) 3) Water temperature: 10 °С/15 °С |
kW | 30.2 |
Cooling capacity СW (actual) 1) 3) Water temperature: 10 °С/15 °С |
kW | 30.2 |
Pressure drop in hydrosystem Water temperature: 10 °С/15 °C3 |
kPa | 109 |
CW system, down flow |
||
Max. presence ESP | Pa | 160 |
Noise level2) | dB | 51.6 |
Power consumption by fans 5) | kW | 1.6 |
CW system, upflow |
||
Max. presence ESP | Pa | 300 |
Noise level2) | dB | 53.1 |
Power consumption by fans5) | kW | 1.8 |
Typical size | 1 |