Technical characterisitis CyberAir 2 С1 |
||
Units CW ( the first circuit of chilled water) | ||
ASD/ASU xxx CW | 660 | |
Air consumption | m3/h | 13.000 |
Cooling capacity CW (full)1) Water temperature: 7 °С/12 °С |
kW | 68,1 |
Cooling capacity CW (actual)1) Water temperature: 7 °С/12 °С |
kW | 54,9 |
Pressure drop in hydrosystem Water temperature: 7 °С/12 °С |
kPa | 100 |
Cooling capacity CW (full) 1) 3) Water temperature: 10 °С/15 °С |
kW | —б) |
Cooling capacity СW (actual) 1) 3) Water temperature: 10 °С/15 °С |
kW | —б) |
Pressure drop in hydrosystem Water temperature: 10 °С/15 °C3 |
kPa | —б) |
CW system, down flow |
||
Max. presence ESP | Pa | 450 |
Noise level2) | dB | 54.5 |
Power consumption by fans 5) | kW | 2.4 |
CW system, upflow |
||
Max. presence ESP | Pa | 300 |
Noise level2) | dB | 055 |
Power consumption by fans5) | kW | 2.7 |
Typical size | 2 |