TICA chiller of TASD-AC2 series 125.1

Chillers and heat pumps with condenser air cooling are designed for water preparation (or solution of unfreezing liquid) for further use in conditioning systems or for production purposes.

Description

модель TASD-AC2
 capacity
125.1
cooling capacity kW 440
kcal/h 378400
power consumption (cooling) kW 146
current power during cooling A 251
max. current at startup A 508
min. working current A 380
power supply   380V — 3Ph -50Hz
evaporator type    direct expansion of cabinet and pipes
speed of cooling by water m3/h 76
size of water pipe DN 125
water pressure kPa 53
limit of water pressure MPa  1.05
 compressor type  semi-hermetic screw
control energy 25%-100% 4-step control
launch control Y-Д
fan air flow m3/h 176000
Qty A 8
 refrigerant type R22
refrigerant quantity in circuit 1
charge mass kg 120+120
 size of unit length mm 150
width mm 5172
height mm 2462
weight of delivery kg 4200
adjustable weight kg 4400