Ice skating rinks
Creating comfortnyh climate conditions in the house is an important criterion for achieving comfort. It is quite difficult to feel comfortable when the room is too hot or too cold. When choosing climate control equipment for the home, special attention should be paid to such parameters as compactness, noise level and reliability.
An excellent choice would be to install mini air-cooled chillers Menergy. They have all the above qualities and are sold at affordable prices. The noise level of these models reaches about 60-65 dB (depending on the power of the selected model). In terms of noise level, these chillers can be compared to a working washing machine.
Product Features:
- Heat pumps for home from Menergy have one or more axial fans in their arsenal, which guarantee the timely supply and removal of air.
- The device uses hermetic compressor, which removes the used R410A refrigerant from the evaporator.
- Compact design. Thanks to the vertical shape of the pumps for the home, they can be installed in basements or boiler rooms without any significant loss of space.
- Protection against overheating and freezing. A system of protective measures has also been implemented to prevent the occurrence of faults associated with voltage surges.
- Technological design.
To order mini chillers for home, using air cooling, contact the company Server-Service. For detailed information on choosing a mini chiller or its operation, please contact the Server-Service company numbers, which you can find in the section “Contacts“.
Technical parameters
Model | MHLR10 | MHLR12 | MHLR16 | MHLR20 | MHLR23 | MHLR30 | MHLR40 | |
Power | Cooling(KW) | 9.6 | 11.5 | 15.8 | 19.2 | 22.8 | 28 | 38 |
EER | 2.82 | 2.80 | 2.93 | 2.82 | 2.78 | 2.76 | 2.79 | |
Heating(KW) | 2.8 | 3.3 | 4.5 | 2.63 | 6.5 | 8 | 11 | |
Power | Heating(KW) | 11 | 12.5 | 16.9 | 22 | 23.8 | 31.5 | 42 |
COP | 3.24 | 3.05 | 3.13 | 3.24 | 2.90 | 3.09 | 3.09 | |
Heating(USRT) | 3.15 | 3.58 | 4.83 | 6.3 | 6.8 | 9 | 12 | |
Electrical parameters | 220/1/50 | 380~420/3/50 | ||||||
Compressor | Type | All closed compressor / Hermetically sealed compressor | ||||||
Power consumption | 3.4 | 4.1 | 2.7×2 | 3.4×2 | 4.1×2 | 3.4×3 | 3.4×4 | |
Pump | Type | Centrifugal | ||||||
Power consumption | 0.46 | 0.5 | 0.6 | 0.72 | 0.72 | 0.96 | 1.00 | |
Flow of water(m) | 19.3 | 17 | ||||||
Evaporator | Type | Plate exchanger / Plate heat exchanger | ||||||
Water consumption (m3/h) | 1.67 | 1.98 | 2.73 | 3.3 | 3.93 | 4.95 | 6.6 | |
Fan | Type | Axis | ||||||
Power consumption (kW) | 0.7 | 0.4 | 0.7×2 | 0.7×3 | 0.7×4 | |||
Protection | overheat,high and low,antifreeze / Protection against overheating, high/low voltage, freezing | |||||||
Coolant | Type | R410A | ||||||
Volume | 3 | 3.3 | 2.9×2 | 3.0×2 | 3.7×2 | 3.0×3 | 3.0×4 | |
Dimensions(mm) | High | 640 | 640 | 1100 | 1280 | 1280 | 1280 | 2560 |
Average | 690 | 690 | 480 | 690 | 690 | 690 | 690 | |
Short | 1300 | 1540 | 1425 | 1300 | 1540 | 1300 | 1300 | |
Pipe diameter(mm) | DN25 | DN23 | DN40 | DN50 | ||||
Noise level dB(A) | 60 | 62 | 65 | |||||
Net weight (Kg) | 120 | 150 | 200 | 230 | 260 | 350 | 400 |
Attention:
- Cooling mode: water inlet/outlet temperature 12℃(53.6℉)/7℃(44.6℉); air temperature 35℃(95℉).
- Heating mode: water inlet/outlet temperature 40℃(104℉)/45℃(113℉); dry/wet bulb temperature 7℃(44.6℉)/6℃(42.8℉).
- Menergy reserves the exclusive right to update parameters.
Server-Service is your reliable partner in creating a comfortable climate in your home, office or enterprise!