Description
Technical characterisitis CyberAir 2 С1 |
||
| Units CW ( the first circuit of chilled water) | ||
| ASD/ASU xxx CW | 1100 | |
| Air consumption | m3/h | 22.000 |
| Cooling capacity CW (full)1) Water temperature: 7 °С/12 °С |
kW | 114,7 |
| Cooling capacity CW (actual)1) Water temperature: 7 °С/12 °С |
kW | 92,6 |
| Pressure drop in hydrosystem Water temperature: 7 °С/12 °С |
kPa | 83 |
| Cooling capacity CW (full) 1) 3) Water temperature: 10 °С/15 °С |
kW | 84,7 |
| Cooling capacity СW (actual) 1) 3) Water temperature: 10 °С/15 °С |
kW | 79,7 |
| Pressure drop in hydrosystem Water temperature: 10 °С/15 °C3 |
kPa | 131 |
| CW system, down flow |
||
| Max. presence ESP | Pa | 120 |
| Noise level2) | dB | 64,8 |
| Power consumption by fans 5) | kW | 5,2 |
| CW system, upflow |
||
| Max. presence ESP | Pa | 110 |
| Noise level2) | dB | 065 |
| Power consumption by fans5) | kW | 5,5 |
| Typical size | 4 | |